Peluang Reduksi Harmonisa Pada Sistem Kelistrikan Gedung B.17 Divisi Biological Product di PT. Medion Farma Jaya
Nadya Intan Pratiwi (2019) | Tugas Akhir | -
Bagikan
Ringkasan
Gedung B.17, Divisi Biological Product di PT. Medion Farma Jaya merupakan bagian yang memproduksi vaksin ternak berlabel Medivac. Dalam kegiatan produksinya digunakan berbagai macam beban nonlinear yang didalamnya terdapat komponen elektronika daya seperti variable speed drive, lampu fluorescent, dan lain-lain. Efek dari penggunaan alat-alat tersebut yaitu menimbulkan permasalahan kualitas daya berupa munculnya gangguan harmonisa dalam sistem tenaga listrik. Pada tugas akhir ini akan dilakukan analisis mengenai peluang reduksi harmonisa pada jenis beban pendingin di Gedung B.17, Divisi Biological Product PT. Medion Farma Jaya. Langkah yang dilakukan yaitu melakukan pengukuran, penentuan batas harmonisa standar, pembandingan harmonisa terukur dengan standar IEEE 519-1992, penentuan upaya pereduksi yang tepat, dan menganalisis peluang reduksi yang dihasilkan oleh pereduksi yang telah ditentukan. Besar harmonisa tegangan hasil pengukuran di MDP induk B.17, MDP B.17B-B, SDP B.17B-B, dan panel beban sesuai dengan standar yang ditentukan. Besar harmonisa arus pada panel beban baik hasil pengukuran maupun simulasi memiliki nilai yang tidak sesuai dengan standar standar IEEE 519-1992, dengan nilai berkisar antara (40-50) %. Upaya yang dinilai tepat untuk mereduksi harmonisa di panel beban dimana beban yang dijadikan sampel adalah mesin AHU 6A, yaitu dengan pemasangan filter pasif. Spesifikasi filter pasif yang digunakan memiliki nilai kapasitansi kapasitor 35 õF untuk mereduksi orde ke-5, 7, dan 11 dan nilai induktansi L= 15 mH untuk mereduksi harmonisa ke 5, L= 6 mH untuk mereduksi harmonisa ke 7, dan L= 2 mH untuk mereduksi harmonisa ke 11. Karakteristik harmonisa pada beban dilihat menggunakan software ETAP 12.6. Pada simulasi beban tanpa filter terukur harmonisa arus sebesar 44,15%. Besar harmonisa arus hasil simulasi pada beban saat menggunakan filter pereduksi harmonisa orde ke-5 adalah 15,59%. Pada saat digunakan dua filter untuk mereduksi harmonisa orde ke-5 dan ke-7 terukur harmonisa arus sebesar 9,46 %. Besar harmonisa arus hasil simulasi menjadi 8,71% saat digunakan filter untuk mereduksi harmonisa arus orde ke-5,7 dan ke-11 secara bersamaan. Reduksi harmonisa dengan filter yang ditentukkan dinilai layak berdasarkan hasil analisis ekonomi teknis dengan, besar saving energy Rp.3.004.597-, / tahun, investasi yang dikeluarkan sebesar Rp.1.200.566-, lama break event point 5 bulan, dan net present value Rp.11.084.989-,. Kata kunci: beban nonlinear, reduksi harmonisa, IEEE 519-1992, potential cost saving, ETAP 12.6.
Ringkasan Alternatif
Building B.17, Biological Product Division at PT. Medion Farma Jaya is a part of producing livestock vaccines labeled Medivac. In its production activities, various types of nonlinear loads are used in which there are power electronic components such as variable speed drives, fluorescent lamps, and others. The effect of using these tools is to cause power quality problems in the form of harmonic interference in the electric power system. In this final project, an analysis of the opportunities for harmonic reduction in the type of cooling load will be carried out in Building B17, Biological Product Division of PT. Medion Farma Jaya. What is done is measuring, determining the standard harmonics, comparing harmonics measured by the IEEE standard 519-1992, determining the appropriate reduction efforts, and the opportunities for reduction that can be done by the predetermined reduction. Large voltage harmonics measured in the main MDP B.17, MDP B.17B-B, SDP B.17B-B, and load panels are below the specified standard. Large current harmonics in the load panel both the measurement results and simulation have values that are not in accordance with the IEEE standard 519-1992, with values ranging from (40-50) %. Efforts that are considered appropriate to reduce harmonics in the load panel where the load being sampled is AHU 6A, which is by fitting passive filters. The passive filter specification used has a capacitance value of 35õF capacitors to reduce 5th, 7th and 11th order and L inductance value = 15mH to reduce the 5th harmonic, L = 6mH to reduce the harmonic to 7th, and L = 2mH to reduce harmonics to 11. Characteristics of harmonics on load are seen using ETAP 12.6 software. In the unfiltered load simulation measured current harmonics of 44.15%. The current harmonics of the load when using the 5th order harmonic reduction filter is 15.59%. When two filters are used to reduce the 5th and 7th order harmonics, current harmonics are measured at 9.46%. Large current harmonics are measured to be 8.71% when a filter is used to reduce the 5th order and 11th order harmonics simultaneously. Harmonic reduction with the specified filter is considered feasible based on the results of the technical economic analysis with, large energy saving Rp. 3,004,597,00 / year, the investment incurred is Rp. 1,200,566,00 long break event point is 5 months, and net present value Rp. 11,084,989,00. Keywords: nonlinear load, harmonic reduction, IEEE 519-1992, potential cost saving, ETAP 12.6.